Fire protection bulkhead systems

Determining a suitable fire protection bulkhead system depends on the size of the wall pipe and medium pipe as well as the movements to be accommodated, as listed in the following table.

System  Nominal diameter Movement
W200x + W200x up to NB 400 wall pipes and
NB 150 medium pipes
for axial and lateral
movements
W200x + W400x up to NB 750 wall pipes and
NB 600 medium pipes
for small axial and
lateral movements
W200x + W410x up to NB 750 wall pipes and
NB 600 medium pipes
for large axial and
lateral movements
Potential
combinations
Wall
pipe
Required sectional
medium pipe insulation
W200x + W200x
Movement
W200x + W400x
Movement
W200x + W410x
Movement
Wall pipe
NB
D1
Medium pipe
NB
D1-2
Thickness ≤
mm
Length
≥ mm
Thickness
≥ mm

mm

mm

± mm

mm

mm

± mm

mm

mm

± mm
50 10 10     15 15 13            
15     14 14 12            
20     12 12 10            
25     9 9 8            
32     6 6 5            
65 15 10     19 19 16            
20     17 17 15            
25     15 15 13            
80 10 10     25 25 22            
15     24 24 20            
20     22 22 19            
25     19 19 17            
100 15 10     33 33 28            
20     31 31 26            
25     28 28 24            
32 400 20 11 11 10            
40 400 20 9 9 8            
125 20 10     39 39 34            
25     37 37 32            
32 400 20 20 20 17            
40 400 20 18 18 15            
50 700 30 7 7 6            
150 32 10 400 20 30 30 26            
40 400 20 28 28 24            
50 700 30 17 17 14            
65 700 30 11 11 10            
80 700 30 7 7 6            
200 40 10 400 20 46 46 39            
50 700 30 35 35 30            
65 700 30 29 29 25            
80 700 30 25 25 21            
100 700 30 16 16 13            
250 65 10 700 30 48 48 41            
80 700 30 43 43 37            
100 700 30 35 35 30            
125 700 30 26 26 22            
150 700 30 16 16 13            
300 65 10 700 30 66 66 56            
80 700 30 61 61 53            
100 700 30 52 52 45            
125 700 30 43 43 37            
150 700 30 33 33 29            
350 80 10 700 30 70 70 60            
100 700 30 63 63 54            
125 700 30 55 55 47            
150 700 30 45 45 38            
200 50 13 13 11            
400 100 10 700 30 70 70 60            
125 700 30 70 70 60            
150 700 30 62 62 53            
200 50       15 15 13 31 31 26
250 50       6 6 5 12 12 10
450 125 6,3 700 30       35 35 30 70 70 60
150 700 30       35 35 30 70 70 60
200 50       24 24 21 48 48 41
250 50       15 15 13 29 29 25
300 50       6 6 5 12 12 10
500 150 6,3 700 30       35 35 30 70 70 60
200 50       33 33 28 66 66 57
250 50       24 24 20 47 47 41
300 50       15 15 13 29 29 25
350 50       9 9 8 18 18 16
550 200 6,3 50       35 35 30 70 70 60
250 50       33 33 28 65 65 56
300 50       24 24 20 47 47 40
350 50       18 18 15 36 36 31
400 50       9 9 8 18 18 16
600 250 6,3 50       35 35 30 70 70 60
300 50       32 32 28 65 65 56
350 50       27 27 23 54 54 46
400 50       18 18 15 36 36 31
450 50       9 9 8 18 18 16
650 300 4,5 50       35 35 30 70 70 60
350 50       35 35 30 70 70 60
400 50       27 27 23 54 54 46
450 50       18 18 15 36 36 31
500 50       9 9 8 18 18 16
700 350 4,5 50       35 35 30 70 70 60
400 50       35 35 30 70 70 60
450 50       27 27 23 54 54 46
500 50       18 18 15 36 36 31
550 50       9 9 8 18 18 16
750 400 4,5 50       35 35 30 70 70 60
450 50       35 35 30 70 70 60
500 50       27 27 23 54 54 46
550 50       18 18 15 36 36 31
600 50       9 9 8 18 18 16

Other nominal bore combinations possible.
The movements listed are based on a concentric position of the medium pipe in relation to the wall pipe
as well as minimal sectional medium pipe insulation thicknesses and a maximum ring gap of 100 mm.
Larger movements on request.